    Technical characteristics:

    Quantity of relay outputs

    2

    Relay commutation voltage, VDC, max.

    30

    Relay commutation current, A, max.

    2

    Calibration interval, months

    12

    Ex marking, TR CU 012/2011

    1 Ex db[ib] IIC T5 Gb X

    Ex marking, ATEX

    II 2G Ex dbib IIC T5 Gb

    Power supply range, VDC

    12…24

    Power consumption, Wt, max.

    2

    Ingress protection

    IP 66

    Communication interface

    RS-485

    Communication protocol

    Modbus

    Analog output range, mA (optional)

    4…20

    Ambient temperature range, °С

    -40…+50

     

    CH4 Measurement Cell Specification (PGU-IK)

    Type

    Infrared

    Detected gas

    Methane

    Measurement range, % vol. (% LEL)

    0…2.2 (0…50)

    Accuracy, % FS vol. (% FS LEL)

    ± 0.22 (± 5)

    Ex marking, TR CU 012/2011

    1 Еx ib IIC Т5 Gb X

    Ingress protection

    IP 54

    Ambient temperature range, °С

    -40…+50

     

    H2S Measurement Cell Specification (PGU-E)

    Type

    Electrochemical

    Detected gas

    Hydrogen Sulphide

    Measurement range, mg/m3 (ppm)

    0…40 (0…28)

    Absolute error range, mg/m3 (within 0…10 mg/m3 measurement range)

    ± 2

    Relative accuracy, % (within 10…40 mg/m3 measurement range)

    ± 20

    Ex marking, TR CU 012/2011

    1 Еx ib IIC Т5 Gb X

    Ingress protection

    IP 54

    Ambient temperature range, °С

    -40…+50

     

    Annunciator Specification

    Number of LEDs

    2

    Sound level, dB

    105

    Ex marking, TR CU 012/2011

    1 Еx ib IIA Т5 Gb X

    Power supply range, VDC

    12…30

    Ingress protection

    IP 65

    Ambient temperature range, °С

    -40…+65

    The GSV-1 Post with a Combined Annunciator is designed for continuous measurement of concentration, for example, methane gas in the air of the working area with the possibility of providing light and sound alarms at two thresholds, e.g. 20% LEL and 50% LEL.

    The Post can be supplied with any of Gas Analyzer from the GSV-1 series.

    The Gas Analyzer can be supplied with digital or analogue output.

     

    Capabilities

    • Interchangeability of sensors of the same type;
    • Explosion-proof protection;
    • Built-in self-diagnosis function.

    Design features

    • Enclosure with a deep cover to protect the display from glare;
    • Informative display;
    • Special color of enclosure depending on the gas detected;
    • The protective visor protects against splashes in the rotary area